ServerNet Cluster 6780 Operations Guide (G06.24+, H06.03+)

Troubleshooting and Replacement Procedures
ServerNet Cluster 6780 Operations Guide525606-002
3-21
Checking the Internal ServerNet X and Y Fabrics
SEBs
1. Using an OSM workstation attached to the node whose internal fabric you want to
check, log on to the OSM Service Connection. The Management window appears.
2. In the tree pane, right-click either Internal_ServerNet_X_Fabric or
Internal_ServerNet_Y_Fabric and select Actions. The Actions dialog box
appears.
3. From the Actions list, select Group Connectivity ServerNet Path Test.
4. Click Perform action. The Action Status window shows the progress of the action.
5. Check for an alarm on Internal_ServerNet_X_Fabric or
Internal_ServerNet_Y_Fabric. If no alarm is present, the action completed
successfully, and ServerNet messages can use the fabric.
6. If an alarm is present, refer to Using OSM Alarms on page 3-11 to identify the
repair actions for the alarm.
Using SCF to Check the Internal ServerNet Fabrics
Use the SCF STATUS SERVERNET command to check processor-to-processor
connectivity for both fabrics within a system:
>SCF STATUS SERVERNET $ZSNET