ServerNet Cluster 6780 Operations Guide (G06.28+, H06.05+)

SCF Commands for the External ServerNet SAN
Manager Subsystem
ServerNet Cluster 6780 Operations Guide525606-003
5-26
Considerations
Considerations
The RESET command is a sensitive command and can be used only by a super-
group user (255, n) ID.
Wild cards are not supported for the RESET command.
RESET SWITCH Command Examples
This example performs a hard reset of the cluster switch in zone 2, layer 1 of the
external ServerNet X fabric:
> RESET SWITCH $ZZSMN, FABRIC X, ZONE 2, LAYER 1, HARD
This command should only be issued by Hewlett-Packard trained support
personnel. Executing this command will force the switch into a hard reset,
which is functionally equivalent to a power-on reset. Before executing this
command, be sure that interprocessor connectivity is up for all nodes through
the other external ServerNet fabric. Note that the switch that is hard reset
will temporarily not be able to respond to further operational commands.
Do you wish to continue with this command? (Y / [N]) Y
The ServerNet switch has been hard reset. To determine when the hard reset
has been completed and the switch is ready for further operational commands,
use the STATUS SWITCH command which will indicate if the switch is
responding. Use the STATUS SUBNET ($ZZSCL) command to determine if
interprocessor connectivity through the switch has returned.