ServerNet Cluster 6780 Operations Guide (G06.28+, H06.05+)
Troubleshooting and Replacement Procedures
ServerNet Cluster 6780 Operations Guide—525606-003
3-5
Hardware Problem Areas
Hardware Problem Areas
Table 3-2 lists some common hardware problem areas, describes troubleshooting 
steps, and provides references for more information.
Table 3-2. Hardware Problem Areas  (page 1 of 4)
Problem Area Symptom Recovery
MSEB Any 1. Use OSM to check for alarms and repair 
actions for the MSEB resource. See Using 
OSM Alarms on page 3-11.
2. Use the OSM Service Connection to perform 
the CRU Responsive Test action on the MSEB.
3. Check the LEDs. See MSEB LEDs
 on 
page 3-26.
4. Check for ServerNet cable and PIC problems 
before you consider replacing the MSEB.
5. See Replacing an MSEB
 on page 3-30.
PIC (installed 
in MSEB only)
Any 1. Use the OSM Service Connection to check the 
PIC Type. Check that the PIC Type is NNA for 
port 6 of the MSEBs installed in slots 51 and 52 
of group 01.
2. Use OSM to check for alarms and repair 
actions for the MSEB resource. See Using 
OSM Alarms on page 3-11.
3. Check the link-alive LEDs. See MSEB LEDs
 on 
page 3-26.
4. If recommended by a service provider or by the 
repair action text for an OSM alarm, perform 
the Internal Loopback Test action on the PIC. 
See Using the Internal Loopback Test Action
 on 
page 3-24.