Electric Code Regulations for Fiber-Optic Cables
Electric Code Regulations for Fiber-Optic Cables
Plenum-rated
Plenum-rated cables are required by some building codes in air plenums to protect
other areas in a building from the transportation of noxious fumes if a fire were to start
or spread through an air plenum. The plenum is the air-handling space between walls,
under structural floors, and above drop ceilings. The fire-resistant and low-smoke
characteristics of a plenum-rated cable allow it to be routed in a plenum area without
being enclosed in a conduit.
Because the plenum-rated cables are ruggedized and have a larger diameter than the
riser-rated cables, a 24-inch breakout is required to allow routing in the cable-
management assembly.
Riser-rated
Riser-rated cables can be used where plenum-rated cables are not required. A riser is
an area that passes between floors. It is normally a vertical shaft or space.
Fiber
Two types of fiber are supported for ServerNet clusters using 6780 switches.
Multimode fiber (MMF)
Multimode fiber is optical fiber designed to carry multiple light rays or modes
concurrently, each at a slightly different reflection angle within the optical fiber core.
Because the modes tend to disperse over longer lengths, multimode fiber transmission
is used for relatively short distances. Multimode fiber has a larger core than single-
mode fiber. The core diameter can be from 50 to 100 microns.
Single-mode fiber (SMF)
Single-mode fiber can be used for high-speed long-distance signal transmission. It
provides greater bandwidth than multimode. SMF is an optical fiber designed for the
transmission of a single ray or mode of light as a carrier. SMF supports only one mode
of light propagation above the cutoff wavelength. SMF has a much smaller core
diameter than multimode fiber. The typical diameter is 8 to 9 microns. The narrow core
allows light to enter only at a single angle.
WARNING. You are required to comply with the National Electric Code (NEC) Article 725 for
installations in the United States and with any local regulations for fiber-optic cables. Neither
the plenum-rated cables nor riser-rated cables are designed to be used in conduits.