ServerNet Cluster Manual
Installing and Configuring a ServerNet Cluster
ServerNet Cluster Manual—520575-003
3-19
Task 9: Perform the Guided Procedure for
Configuring a ServerNet Node
•
Make sure the ferrule housing and the ceramic ferrule tip are visible. The
ferrule housing should be at least flush with the connector housing.
•
It is normal for the ferrule housing to slide freely (approximately 2 mm) within
the connector body between the stops designed into the connector-body
assembly.
•
If the ferrule housing and ceramic ferrule tip are pushed back inside the
connector body, the connector might be defective and you should obtain
another cable.
4. Align the keys on the connector body with the key slots on the receptacle of the
MSEB or ServerNet II Switch.
Figure 3-2. Inspecting Fiber-Optic Cable Connectors
Note. The key slots on ports 8 through 11 of the ServerNet II Switch are located at the top
of the receptacle. On ports 0 through 7, the key slots are located at the bottom of the
receptacle. See Figure 3-3
.
VST003.vsd
Defective
Connector
(DO NOT USE)
Good
Connector
Connector
Body
Ceramic
Ferrule Tips
Ferrule
Housing