Virtual TapeServer 6.04.02 for NonStop Servers Quick Setup Guide

Virtual TapeServer Quick Setup Guide | 21
HIGH LEAKAGE CURRENT
To reduce the risk of electric shock due to high leakage currents, a reliable grounded (earthed)
connection should be checked before servicing the power distribution unit (PDU).
Observe the following limits when connecting the product to AC power distribution devices: For
PDUs that have attached AC power cords or are directly wired to the building power, the total
combined leakage current should not exceed 5 percent of the rated input current for the device.
“HIGH LEAKAGE CURRENT, EARTH CONNECTION ESSENTIAL BEFORE CONNECTING
SUPPLY”
“HOHER ABLEITSTROM. VOR INBETRIEBNAHME UNBEDINGT
ERDUNGSVERBINDUNG HERSTELLEN”
“COURANT DE FUITE E’LEVE’. RACCORDEMENT A LA TERRE INDISPENSABLE AVANT
LE RACCORDEMENT AU RESEAU”
FUSE REPLACEMENT
CAUTION – For continued protection against risk of fire, replace fuses only with fuses of the
same type and the same rating. Disconnect power before changing fuses.
Important Safety Information
Safety information is located in two places.
HP NonStop NS-Series Servers
Safety information is available from the NTL home page. Select Safety and Compliance >
Important Safety Information. To open the safety information in a language other than English,
select the language. Local HP support can also help direct you to your safety information.
HP NonStop S-Series Servers
Customer Installation and Servicing of Equipment
The following statements pertain to safety issues regarding customer installation and servicing
of equipment described in this manual.
Keep door closed for normal operation.
The equipment must be installed near the receptacles for the power cords, and the
receptacles must be easily accessible to the user.
Applicability of Procedures, Instructions, and Examples
Do not touch the DC power connector on the S7400/S7x000 PMF CRU after you have
unplugged the DC power cable from the CRU. It is possible to incur a severe energy
hazard for as long as fifteen (15) seconds after unplugging the cable. You can make sure
the CRU is safe to remove by testing (by using a volt meter) before touching the pins on
the DC power connector.
WARNING! The procedures and instructions and the examples of procedures and
instructions found in this manual apply only to the system enclosures and components
found in Himalaya S-series servers which are described in the Himalaya S-series server
documentation. Do not attempt to use these instructions with any other Tandem NonStop
system equipment. You can determine that your system is a Himalaya S-series server by
reading the label that appears inside each system enclosure on the CRU in slot 50 or 55.
The label includes the product number 1980. Read the label before proceeding with any
procedure or instruction found in this manual.