HP Performance Optimized Datacenter 20c User Guide - China

Power, electrical, and controls 23
Capacities
HP POD 20c capacity limitations
The capacity limitations for the HP POD 20c are separated into two categories: electrical power and
mechanical cooling capacities. Both of these categories are interdependent and must be considered in
conjunction with the overall customer requirements.
Electrical and mechanical cooling capacities
Feature Specification
Critical IT electrical
connections
2 x 400 A feeders at 380-415 VAC Y, 3-Phase, at
50-60 Hz with equipment ground conductors
2 x 3 in (5.1 x 7.6 cm) conduit fittings per feeder
provided
Critical IT power
capacity
Non-redundant263 - 288 kW
2N Redundant132 - 144 kW
Mechanical cooling
electrical connections
Not applicable
Power for the cooling system fans comes from house
power.
Mechanical cooling
capacity
Not applicable
The POD is electrically limited regardless of the
redundancy level.
Power feeders
IMPORTANT:
A licensed electrician must connect the power according to all local and national
electrical codes, and must comply with manufacturer specifications.
The HP POD 20c has two power feeder couplings that provide the entrance for power to the POD. The power
feeders route into the end of the HP POD 20c.
Side view shown