Environmental control system 53
Perform the following tasks on this screen:
Configure the IP address for each power meter
Control the fans in each zone
Control the valve
Configure the HP POD 20c serial number
Configure the switchboard serial number
Calibrate the flowmeter
Calibrate the chilled water and differential pressure sensors
Enable or disable power measurement
You must select Save to store the parameter changes in the system configuration file. If you do not save your
changes, the old parameters stored in the configuration file reload when the system starts.
Configuring the fan current
Fan current tolerance
The fan current tolerance parameters appear on the related buttons.
To configure the fan current tolerance parameters:
1. Select Fan Current Tolerance.
A keypad appears.