HP Performance Optimized Datacenter 20c User Guide - China
Cooling system 63
Feature Specification
HP POD 20c pressure drop
172.4 kPa (25 psi)
HP POD 20c water flow rate
454 lpm (120 gpm)
Chilled water supply and return
connections
Two DIN PN16 DN80 flanges
Cooling system components
Each of the three heat exchanger area access hatches are rated NEMA 3R for outdoor use. The exterior of
the hatches are coated with a durable finish to protect against corrosion. The access hatches are located on
the roof of the POD. The heat exchangers can be accessed from the roof of the POD by removing one of the
six access hatches.
Top view shown
Item Component Description
1
Heat exchangers Uses chilled facility water to cool the air in the HP POD 20c
2
Chilled water supply
header
Provides cooled chilled water from the site chilled water system to the heat
exchangers
3
Chilled water return
header
Provides heated chilled water to the return site chilled water system