Power, electrical, and controls 25
Capacities
HP POD 20c capacity limitations
The capacity limitations for the HP POD 20c are separated into two categories: electrical power and
mechanical cooling capacities. Both of these categories are interdependent and must be considered in
conjunction with the overall customer requirements.
Electrical and mechanical cooling capacities
Feature Specification
Critical IT electrical
connections
2 x 400 A feeders at 480VAC Delta, 3-Phase, 3-
wire,
with equipment ground conductors
2 x 4 in (5.1 x 10.2 cm) conduit fittings per feeder
provided
Critical IT power
capacity
•
Non-redundant—288 kW
•
2N Redundant—144 kW
Mechanical cooling
electrical connectors
Not applicable
Power for the cooling system fans comes from the
critical IT power feeds.
Mechanical cooling
capacity
•
Non-redundant—300 kW
•
2N Redundant—150 kW
Power feeders
IMPORTANT: A licensed electrician must connect the power according to all local and national
electrical codes, and must comply with manufacturer specifications.
The HP POD 20c has two power feeder couplings that provide the entrance for power to the POD. The power
feeders route into the top of each electrical panel on the side of the HP POD 20c.