Power, electrical, and controls 30
power source and from common switchboards and transformers. A 2N redundancy installation is configured
by feeding the parallel power paths from independent power sources, switchboards, and transformers.
Non-redundant power installation (1N load)Both main input connections to the HP POD 20c are
powered from the same power feed.
Redundant power installation (2N load)Each main input connection to the HP POD 20c is powered
from parallel power paths from independent power feeds.
Drop boxes
The internal electrical busways provide a location to connect each of the drop boxes, which then power the
PDUs. Stagger the drop boxes on the electrical busways by connecting one drop box to busway #1 and
connecting the next drop box to busway #2. A staggered configuration enables load balancing with the rack
equipment and is necessary to ensure redundancy.