HP Performance Optimized Datacenter 20c User Guide - North America

Power, electrical, and controls 32
Feature Specification
Rack type
HP POD rack
Max number of racks
10
Max U space per rack
50U
Max U space per HP POD 20c
500U
Server capacity
288 kW power capacity
Average capacity per rack
28.8 kW
Peak capacity per rack
69 kW
Voltage to rack
240 VAC
Rack configuration
Redundant/Non-redundant
capabilities
Total number of PDU's
20 (two per rack)
Max power per PDU
30 A = 17 kW; 60 A = 34 kW
Max load (Chilled POD cooling mode)
*
288 kW
Airflow per rack (Chiller POD cooling
mode)
1,200 CFM
*
Dependent on configuration
HP POD 20c lighting
The HP POD 20c includes six fluorescent lights. Three lights are located in the cold aisle and three lights are
located in the hot aisle.
A light switch is located at the personnel access door.
One light in the cold aisle is connected to battery backup power, keeping the interior of the HP POD 20c
illuminated during a power outage or emergency.
For more information on lighting, see the HP Performance Optimized Datacenter 20c Maintenance and
Service Guide.