HP Performance Optimized Datacenter 20c User Guide - North America

Environmental control system 46
-
You can select and configure the following parameters:
Cold aisle temperature alarm
Hot aisle temperature alarm
Humidity alarm
Differential pressure alarm
Chilled water supply pressure
Chilled water supply temperature
Chilled water return temperature
Type of units displayed
Control the fans in each zone
Configure the IP address
You must select Save to store the parameter changes in the system configuration file. If you do not save your
changes, the old parameters stored in the configuration file reload when the system starts.
Configuring the cold aisle temperature alarm parameters
The current temperature parameters appear on the related buttons.
To configure the cold aisle low temperature alarm parameters:
1. Select Cold Aisle Low Alarm Temperature.