HP Performance Optimized Datacenter 20c User Guide - North America

Environmental control system 51
The Advanced System Configuration screen displays fan current setpoints, calibration options, and other
details about the HP POD 20c.
Perform the following tasks on this screen:
Configure the fan current setpoints
Calibrate the flowmeter
Calibrate the chilled water and differential pressure sensors
Enable or disable power measurement
Configure the IP address for each power meter
Configure the switchboard serial number
Configure the HP POD 20c serial number
Set the logging configuration
You must select Save to store the parameter changes in the system configuration file. If you do not save your
changes, the old parameters stored in the configuration file reload when the system starts.
Configuring the fan current
Fan current tolerance
The fan current tolerance parameters appear on the related buttons.