HP Performance-Optimized Datacenter, 6 m (20 ft) User Guide
Installation 18
• Verify accurate electrical installation.
• Verify accurate mechanical installation.
• Test the operation of the ECS and Cooling controls.
• Test the operation of the smoke detection system.
• Test the operation of EPO system.
• Test the operation of the analog and digital phone system (optional).
• Verify initial IT start-up.
• Conduct an infrared scan of all electrical connections under the start-up IT load.
• Verify accurate cooling under start-up IT load.
• Provide the HP POD operation owner training.