HP Performance-Optimized Datacenter, 6 m (20 ft) User Guide
Control and power panels 20
HP POD transformers and circuit breakers
Item Component Description
1 House panel circuit breaker House panel A bus circuit breaker
2 100A house panel feeder breaker House panel A feeder circuit breaker
3 Busway feeder breaker
225A electrical panel board for electrical busway
A
4 House panel circuit breaker House panel B bus circuit breaker
5 100A house panel feeder breaker House panel B feeder circuit breaker
6 Busway feeder breaker
225A electrical panel board for electrical busway
B
7 480V delta to 415 wye transformer Integrated 480V delta to 415V wye transformer A
8 480V delta to 415 wye transformer Integrated 480V delta to 415V wye transformer B
Control panel components
The actual location of various components or subsystems in your HP POD might vary from this
documentation. For final placement specifications, see your operations and maintenance manual.