HP Performance-Optimized Datacenter, 6 m (20 ft) User Guide

Power management 29
The internal electrical busways provide a location to connect each of the dropboxes, which then power
the PDUs. The dropboxes should be staggered on the electrical busways; one connected to the A-side
busway and the next connected to the B-side busway.
Disabling power
To disable power to a single PDU, open the drop box breaker feeding that PDU and disconnect the
PDU from the drop box.
To disable power to a single rack, open the corresponding breakers on the drop boxes feeding each
of the PDUs installed in that rack.
To disable power to a single electrical busway, open the appropriate main breaker for that busway
on the corresponding electrical busway panel outside of the HP POD.
Power distribution: Electrical busway enclosed circuit panels
The HP POD is powered by electrical busways on the end of the unit.
Feature Specification
Number of busways 2