HP Performance-Optimized Datacenter, 6 m (20 ft) User Guide
Power management 30
Feature Specification
Frequency 50—60 Hz
Amps (per busway) 225A
Neutral ampacity (per breaker) 225A
Amps derated percentage 10%
Max usable amps (per busway) 202A
Voltage (per busway) 380-415V
Grounding Aluminum casing
Busway conductors 3 phases + neutral
NA standard density HP POD capacities
Feature Capacity
Tier 1 configuration 450 kW
N + N configuration 291 kW
3 phase PDU capacity 17.28 kW
Thermal capacity limit 450 kW
International standard density HP POD capacities
Feature Capacity
Tier 1 configuration 450 kW
N + N configuration 291 kW
3 phase PDU capacity 22 kW
Thermal capacity limit 450 kW
Power distribution: Dropboxes, PDUs, and racks
NA HP POD configurations
Configuration
Number of 3-
phase PDUs per
HP POD
Number of
dropboxes per
HP POD
Maximum power
capacity per rack
Total HP POD
power capacity
4 x 225
Nonredundant
20 10 34.56 kW 291 kW
4 x 225
Redundant
20 10 17.28 kW 145 kW
International HP POD configurations
Configuration
Number of 3-
phase PDUs per
HP POD
Number of
dropboxes per
HP POD
Maximum power
capacity per rack
Total HP POD
power capacity
4 x 225
Nonredundant
20 10 44 kW 291 kW
4 x 225 20 10 22 kW 145 kW