HP Performance-Optimized Datacenter, 6 m (20 ft) User Guide
Environmental control system 39
Advanced system configuration
Item Description
Fan current setpoints
Indicates fan current set points and enables you to adjust values for fan
monitoring
Calibrate flowmeter Enables flow rate calibration based on the value of a calibrated flow meter
Calibrate chilled water
sensor
Is accessible only when the flow rate is zero and the chilled water pressure on
chilled water supply and return lines is less than 12.75 psi. (1.5 bar)
Calibrate differential
pressure sensors
Is accessible when all fans and the IT load are off and there is no air flowing
inside the HP POD
Power measurement
(Optional)
Shows when power measurement is active within the HP POD
Switchboard serial number Displays the serial number for the HP POD switchboard
HP POD serial number Displays the serial number for the HP POD