HP Performance-Optimized Datacenter, 6 m (20 ft) User Guide

Specifications 49
Feature Specification
U height 50U
Width 546 mm (21.5 in)
Depth 1,000 mm (39.4 in)
Maximum load weight 1,360.7 kg (3,000 lb)
Thermal and air flow performance
Maximum thermal and air flow
performance parameters
HP POD specification
Air temperatureInlet to rack-
mounted components
Hot aisle setpoint temperature in ECS
Chilled water temperature 12°24°C (55°75°F)
Total rack-mounted component air
flow
Variable as required to maintain hot
aisle setpoint temperature
Heat rejection capacity 600 kW
Environmental specifications
Features Specifications
Operating temperature -18ºC to 54ºC (0ºF to 130ºF).
Supports to -29ºC (-20ºF) with optional cold weather
protection installation.
Nonoperating
temperature*
-29ºC to 54ºC (-20ºF to 130ºF)
Operating humidity
0% to 100% relative noncondensing
Nonoperating humidity*
5 to 95% relative noncondensing
39ºC (102ºF) maximum wet bulb temperature
Operating altitude -76.2 to 3,048 m (-250 to 10,000 ft)
Non-operating altitude -76.2 to 9,144 m (-250 to 30,000 ft)
*For nonoperating specifications, consider the temperature of computer and IT equipment inside the HP POD.
The HP POD must be drained before it is moved to a new location.
For areas prone to freezing, take appropriate water freeze protection precautions.