HP Performance-Optimized Datacenter, 6 m (20 ft) User Guide

Appendix 53
Appendix
I/O controls points list
The points list table is a sample of possible point information. The information included might be different
for your site and customized HP POD.
The following table is an example. For an accurate listing of point information, see your operator and
maintenance documentation.
Electrician/ Fitter
Point Information
Controller Information
Panel Information
Controller
Point
Type
Object
Name
Expanded ID
Controller
Details
Trunk
Type
Cable
Destinatio
n Bay
Panel
Detail
Reference
Cable
Number
NCE UI IN-1 CA1-T
Cold aisle
Zone 1
Temperature
NCE25xx
MS/T
P
UI IN-1 F131
1-4-UI IN-
1
NCE UI IN-2 CA2-T
Cold aisle
Zone 2
Temperature
NCE25xx
MS/T
P
UI IN-2 F131
1-4-UI IN-
2
NCE UI IN-3 CA3-T
Cold aisle
Zone 3
Temperature
NCE25xx
MS/T
P
UI IN-3 F131
1-4-UI IN-
3
NCE UI IN-4 CA4-T
Cold aisle
Zone 4
Temperature
NCE25xx
MS/T
P
UI IN-4 F131
1-4-UI IN-
4
NCE UI IN-5 CA5-T
Cold aisle
Zone 5
Temperature
NCE25xx
MS/T
P
UI IN-5 F131
1-4-UI IN-
5
NCE UI IN-6 CA6-T
Cold aisle
Zone 6
Temperature
NCE25xx
MS/T
P
UI IN-6 F131
1-4-UI IN-
6
NCE UI IN-7 ZN1- DP
Zone 1
Differential
Pressure
NCE25xx
MS/T
P
UI IN-7 F106
1-4-UI IN-
7
NCE UI IN-8 ZN2- DP
Zone 2
Differential
Pressure
NCE25xx
MS/T
P
UI IN-8 F106
1-4-UI IN-
8
NCE UI IN-9 ZN3- DP
Zone 3
Differential
Pressure
NCE25xx
MS/T
P
UI IN-9 F106
1-4-UI IN-
9
NCE UI IN-10 ZN4- DP
Zone 4
Differential
Pressure
NCE25xx
MS/T
P
UI IN-10 F106
1-4-UI IN-
10