HP Performance-Optimized Datacenter, 6 m (20 ft) User Guide
Appendix 58
IOM4
CO OUT-
6
Unused Unused IOM 4710
SA
Bus
CO OUT-6 Unused
4-1-7-CO
OUT-6
IOM4
CO OUT-
7
Unused Unused IOM 4710
SA
Bus
CO OUT-7 Unused
4-1-7-CO
OUT-7
IOM4
AO OUT-
8
Unused Unused IOM 4710
SA
Bus
AO OUT-8 Unused
4-1-7-AO
OUT-8
IOM4
AO OUT-
9
Unused Unused IOM 4710
SA
Bus
AO OUT-9 Unused
4-1-7-AO
OUT-9
IOM5 UI IN-1 ZN5-DP
Zone 5
Differential
Pressure
IOM 4710
SA
Bus
UI IN-1 F106
4-1-8-UI
IN-1
IOM5 UI IN-2 ZN6-DP
Zone 6
Differential
Pressure
IOM 4710
SA
Bus
UI IN-2 F106
4-1-8-UI
IN-2
IOM5 UI IN-3
FanBank
9-I
Fan Bank 9
Current
IOM 4710
SA
Bus
UI IN-3 F106
4-1-8-UI
IN-3
IOM5 UI IN-4
FanBank
10-I
Fan Bank 10
Current
IOM 4710
SA
Bus
UI IN-4 F106
4-1-8-UI
IN-4
IOM5 UI IN-5
FanBank
11-I
Fan Bank 11
Current
IOM 4710
SA
Bus
UI IN-5 F106
4-1-8-UI
IN-5
IOM5 UI IN-6
FanBank
12-I
Fan Bank 12
Current
IOM 4710
SA
Bus
UI IN-6 F106
4-1-8-UI
IN-6
IOM5 BI IN-7 Unused Unused IOM 4710
SA
Bus
BI IN-7 Unused
4-1-8-BI
IN-7
IOM5 BI IN-8 Unused Unused IOM 4710
SA
Bus
BI IN-8 Unused
4-1-8-BI
IN-8
IOM5
BO OUT-
1
Unused Unused IOM 4710
SA
Bus
BO OUT-1 Unused
4-1-8-BO
OUT-1
IOM5
BO OUT-
2
Unused Unused IOM 4710
SA
Bus
BO OUT-2 Unused
4-1-8-BO
OUT-2
IOM5
BO OUT-
3
Unused Unused IOM 4710
SA
Bus
BO OUT-3 Unused
4-1-8-BO
OUT-3
IOM5
CO OUT-
4
Unused Unused IOM 4710
SA
Bus
CO OUT-4 Unused
4-1-8-CO
OUT-4
IOM5
CO OUT-
5
Unused Unused IOM 4710
SA
Bus
CO OUT-5 Unused
4-1-8-CO
OUT-5
IOM5
CO OUT-
6
Unused Unused IOM 4710
SA
Bus
CO OUT-6 Unused
4-1-8-CO
OUT-6
IOM5
CO OUT-
7
Unused Unused IOM 4710
SA
Bus
CO OUT-7 Unused
4-1-8-CO
OUT-7
IOM5
AO OUT-
8
Unused Unused IOM 4710
SA
Bus
AO OUT-8 Unused
4-1-8-AO
OUT-8
IOM5
AO OUT-
9
Unused Unused IOM 4710
SA
Bus
AO OUT-9 Unused
4-1-8-AO
OUT-9