HP Performance Optimized Datacenter (POD) 20c Site Preparation and Requirements Guide - China

Supported facility connections 20
IMPORTANT: Confirm with the AHJ that condensate water and rain water can be mixed in the
same drainage.
HP POD 20c security
The HP POD 20c is equipped with standard key lock hardware for each personnel entry door and external
electrical cabinet. Each personnel entry door includes a door access contact that can be connected to the
customer facility security system.
Additional options for controlled access security include the following:
Electronic card reader
12-digit security code keypad
Magnetic lock on each personnel entry door and dynamic hot aisle door
Fire, safety, and security notifications
Dry contacts are provided to enable the connection between the HP POD 20c fire alarm system and the
customer facility fire system. If the HP POD 20c is connected to the customer facility systems, then the alarms
initiated by the HP POD 20c notify the facility systems.
It is your responsibility to facilitate these connections. HP can make these connections when specifically
contracted to deliver these services and a Scope of Work has been drafted, reviewed, and signed for
delivery services.
The customer must provide an independent connection for each system listed in the following table.
Alarm Description
Fire prevention alarm
Smoke is detected in the HP POD 20c.
Fire suppression
system (optional)
The suppression system alarm is activated and gas is
dispersed to suppress a fire.
Security
A security breach occurred.
EPO
The EPO system is activated by manually pressing the
EPO button or by a thermal event, and the HP POD 20c
is shut down.
The electrical layout of the fire alarm system is described in the schematic drawing that is supplied with the
HP Performance Optimized Datacenter 20c Site Drawing Package.