HP Performance Optimized Datacenter (POD) 20c Site Preparation and Requirements Guide - China

Environmental considerations 21
Environmental considerations
Environmental risks
Avoid placing the HP POD 20c directly along a drainage path or in an area prone to flooding.
Verify that the HP POD 20c is properly grounded in accordance with national, regional, and local
regulations, ordinances, codes, and the product specifications.
Cold weather
The HP POD 20c requires a site chilled water supply and return, humidifier supply and drain, and
condensate drains. Extreme cold weather can cause damage to the supply and drain lines. Evaluate the
following for additional cold weather protection:
Regional location of the HP POD 20c
Exposure of the supply and drain lines to extreme cold temperatures
Extreme cold weather can affect crane and lifting operations. When temperatures drop below -12.2°C
(10°F), appropriate consideration must be made with respect to shock loading, crane hydraulics, and
possible de-rating of the crane.
Areas prone to lightning or power surges
The HP POD 20c structure and internal components are all bonded together. A common grounding electrode
conductor connection point is provided. Properly bonding and grounding of the HP POD 20c minimizes the
effects of a lightning strike. A surge protection device is provided on the HP POD 20c input connection to
protect the HP POD 20c electrical system from voltage transients. If your site is in an area that is subject to
frequent lightning strikes, the HP POD 20c must be protected per all national, regional, and local regulations,
ordinances, codes, and the product specifications. HP recommends that you contact a certified lightning
protection consultant.
Seismic activity
If your site is in an area that has frequent seismic activity, HP recommends that you contact a seismic activity
consultant. If your site is in an area that has high vibration level, HP recommends that you contact a vibration
isolation consultant. You must specify the method of anchoring the HP POD 20c, if necessary.