HP Performance Optimized Datacenter (POD) 20c Site Preparation and Requirements Guide - China

Site plan requirements and actions 24
Assembly equipment locations
HP POD 20c lifting requirements
WARNING: The only approved method for lifting the HP POD 20c is the use of a spreader bar
harness. Lifting an HP POD 20c in any other manner can cause damage to the HP POD 20c and
void your warranty.
HP POD 20c storage requirements
If the site is not ready for assembly and operation, determine a location for storage when creating the site
plan.
CAUTION: The HP POD 20c must maintain 20% relative humidity to minimize condensation and
oxidation within the HP POD 20c.
CAUTION: While being stored, the HP POD 20c must be kept in a level position even if stored
on a trailer.
Changes in ambient temperatures can cause condensation in a non-operational HP POD 20c. If the HP POD
20c is placed in storage or is in non-operating mode for over 72 hours, HP recommends using one of the
following methods to minimize condensation and oxidation within the HP POD 20c:
Desiccant unit
Desiccant material
Heater with a fan
Air conditioner with a heater strip
Consult with HP Services to determine the most effective method.
Additional structures
If a customer-provided vestibule or other structure is installed and connected to the HP POD 20c, the following
specifications must be maintained:
To protect the HP POD 20c and ensure a waterproof barrier, flashing must be installed to the exterior
of the HP POD 20c in the location where the other structure is attached.