HP Performance Optimized Datacenter (POD) Networking Guide

Addressing airflow with HP Network Switchbox Enclosure Kit (SKU AT053A) 12
Cisco Catalyst 6500-E
This device requires 2RU minimum space below and 3RU above the chassis. The device also requires a
Network Switchbox Enclosure Kit (SKU AT053A) and an HP Network Switch Enclosure Side panel Kit (SKU
AT960A). The Cisco Catalyst 6500-E does not require a side panel kit on the exhaust side of the chassis.
To enable adequate airflow along the top, bottom, and side of the air-inlet side of the chassis, the 6500-E
must be placed on a support rail and secured to the rack with custom mounting brackets, allowing the chassis
to be recessed in the rack. Care must be taken to also maintain hot and cold air-flow separation. The 6500
series switches have complex air flow and will require additional parts and customization for successful
operation. The account SA is responsible for engaging directly with the POD network SA for additional
guidance.
Other hardware considerations
To maintain hot and cold air seperation while the TFT is in the open position, you must place TFT and KVM
devices inside an HP Network Switchbox Enclosure Kit (SKU AT053A).
NOTE: The HP Network Switch Enclosure Kit (SKU AT053A) can be fully collapsed to a minimum
of 3RU.