HP Performance Optimized Datacenter (POD) 40c G2 Maintenance and Service Guide
Periodic maintenance 67
Fire alarm and suppression system
Component to be inspected Task Frequency Capable Party
Full system functional check
Inspect and perform a functional
check of the system.
As required by
local code
Licensed fire safety
contractor
—
Inspect and test fire panel
battery backup system.
Bi-annually Licensed fire safety
contractor
—
Inspect and test VESDA power
supply.
Quarterly Licensed fire safety
contractor
—
Inspect the VESDA pipe
network.
Bi-annually Licensed fire safety
contractor
—
Inspect the VESDA filter. Annually Certified facilities
personnel
—
Conduct a VESDA pipe integrity
smoke test.
Annually Licensed fire safety
contractor
—
Check the VESDA pipe flow. Annually Licensed fire safety
contractor
—
Clean the VESDA sampling
points.
Every 2 years Licensed fire safety
contractor
—
Flush the VESDA pipe network. Every 2 years Licensed fire safety
contractor
—
VESDA system air
sampling/smoke test
As required by
local code
Licensed fire safety
contractor
—
Suppression system test As required by
local code
Licensed fire safety
contractor
—
Fire-pull visual and operational
inspection
As required by
local code
Licensed fire safety
contractor
—
Fire strobe and horn visual and
operational inspection
As required by
local code
Licensed fire safety
contractor
Generator (if applicable)
Component to be inspected Task Frequency* Capable Party
Generator
Visual inspection of the generator Quarterly HP and certified
facilities personnel
—
Oil change Annually HP
—
Oil filter change Annually HP
—
Oil analysis Annually HP
—
Fuel filter change Annually HP
—
Coolant freeze point and
inhibition check each time the
generator is viewed
— HP
*These are typical frequencies. See the documentation for the installed component for the recommended schedule.