HP Performance-Optimized Datacenter, 12 m (40 ft) User Guide
Power management 26
The internal electrical busways provide a location to connect each of the drop boxes, which then power
the PDUs. Stagger the drop boxes on the electrical busways; one connected to the A-side busway and the
next connected to the B-side busway.
Disabling power
• To disable power to a single PDU, open the drop box breaker feeding that PDU and disconnect the
PDU from the drop box.
• To disable power to a single rack, open the corresponding breakers on the drop boxes feeding each
of the PDUs installed in that rack.
• To disable power to a single electrical busway, open the appropriate main breaker for that busway
on the corresponding electrical busway panel outside of the HP POD.
Power distribution: Electrical busway enclosed circuit breaker
panels
Standard density HP POD
The standard density HP POD is protected by electrical circuit breaker panels that are located on both
ends of the HP POD.