HP Performance-Optimized Datacenter, 12 m (40 ft) User Guide
Power management 27
Feature Specification
Number of busways 4
Frequency 50-60 Hz
Amps (per busway) 225A
Neutral ampacity (per breaker) 225A
Amps derated percentage 10%
Max usable amps (per busway) 202A
Voltage (per busway) 380-415V
Grounding Aluminum casing
Busway conductors 3 phases + neutral
NA standard density HP POD capacities
Feature Capacity
Tier 1 configuration 450 kW
N + N configuration 291 kW
3 phase PDU capacity 17.28 kW
Thermal capacity limit 450 kW
International standard density HP POD capacities
Feature Capacity
Tier 1 configuration 450 kW
N + N configuration 291 kW
3 phase PDU capacity 22 kW
Thermal capacity limit 450 kW
High density HP POD
The high density HP POD is protected by electrical circuit breaker panels that are located at both ends
and in the center of the HP POD.
Feature Specification
Number of busways 6
Frequency 50-60 Hz