HP Performance-Optimized Datacenter, 12 m (40 ft) User Guide

Power management 28
Feature Specification
Amps (per breaker) 225A
Neutral ampacity (per breaker) 225A
Amps derated percentage 10%
Max usable amps (per breaker) 202A
Voltage (per busway) 380-415V
Grounding Aluminum casing
Busway conductors 3 phases + neutral
NA high density HP POD capacities
Feature Capacity
Tier 1 configuration 600 kW
N + N configuration 380 kW
3 phase PDU capacity 17.28 kW
Thermal capacity limit 600 kW
International high density HP POD capacities
Feature Capacity
Tier 1 configuration 600 kW
N + N configuration 436 kW
3 phase PDU capacity 22 kW
Thermal capacity limit 600 kW
Power distribution: Dropboxes, PDUs, and racks
NA standard density HP POD configurations
Configuration
Number of 3
phase PDUs per
HP POD
Number of
dropboxes per
HP POD
Power capacity
per rack
Total HP POD
power capacity
4 x 225
Non-redundant
22 11 17.28 kW 450 kW
4 x 225
Redundant
44 22 17.28 kW 291 kW
International standard density HP POD configurations
Configuration
Number of 3
phase PDUs per
HP POD
Number of
dropboxes per
HP POD
Power capacity
per rack
Total HP POD
power capacity
4 x 225
Non-redundant
22 11 22 kW 450 kW
4 x 225
Redundant
44 22 22 kW 291 kW