HP Performance-Optimized Datacenter, 12 m (40 ft) User Guide

Power management 29
NA high density HP POD configurations
Configuration
Number of 3
phase PDUs per
HP POD
Number of
dropboxes per
HP POD
Power capacity
per rack
Total HP POD
power capacity
6 x 225
Non-redundant
44 22 44 kW 600 kW
6 x 225
Redundant
44 22 17.28 kW 380 kW
International high density HP POD configurations
Configuration
Number of 3
phase PDUs per
HP POD
Number of
dropboxes per
HP POD
Power capacity
per rack
Total HP POD
power capacity
6 x 225
Non-redundant
44 22 44 kW 600 kW
6 x 225
Redundant
44 22 22 kW 436.5kW
Rack power
Power is provided to each rack by PDUs and drop boxes. The PDUs are powered by the drop boxes
attached to each electrical busway.
For more information regarding power shortages to the PDUs or electrical busway drop boxes, see
Troubleshooting (on page 43).