HP Performance-Optimized Datacenter, 12 m (40 ft) User Guide

Environmental control system 37
8.
Log in to Johnson Controls.
9. To view the status points:
a. Select the All Items tab on the left side of the page.
b. Select the User Views folder. Click the + to expand the folder and see the subcategories.
c. Select any subcategory to view its status and description.
ECS alarms
The alarms pertaining to the health of the HP POD and its components are relayed through the ECS.
Alarm Meaning Solution
Fan failure One of the fans is not working.
If you are still within your service
contract, contact HP service.
Sensor failure One of the sensors is not working.
If you are still within your service
contract, contact HP service.
Leak detection The drain tray senses water.
Inspect drain trays to determine if
water is from normally occurring
condensation. If leak is not from
normally occurring condensation, then
perform the following steps:
1 Turn off all IT components, so that
the components do not overheat.
2 Turn off the water flowing into
your HP POD at the facility line.
3 If you are still within your service
contract, contact HP service.