HP Performance-Optimized Datacenter, 12 m (40 ft) User Guide
Specifications 45
Features Specifications
Maximum weight
11,340 kg (25,000 lb) empty- 50,348 kg (111,000 lb) fully-
loaded
Maximum power/ cooling 600 kW Standard HP POD
Maximum rack quantity 22 racks
Rack Units (RU) per rack 50 RU
Rack Units (RU) total 1100 RU
Nominal power/ cooling per rack
Nonredundant mode
27.27 kW – North America & International
Nominal power/ cooling per rack
Redundant mode
17.28 kW – North America
19.84 kW – International
Maximum power/ cooling per rack
Nonredundant mode
34.56 kW – North America
44 kW – International
Maximum power/ cooling per rack
Redundant mode
17.28 kW – North America
22 kW – International
Power input voltage
380-415 Wye connected, 225A, 3 Phase, 50/60 Hz, with
neutral (6 feeders required)
Power distributed internally 6 225A electrical busways
220-240/380-415 VAC, 50/60 Hz
Customer access Double-door on one end
Customer access—Two 1 m x 2.1 m (3 ft x 7 ft) doors to the
cold aisle
Rear component access—Four 1.8 m x 2.1 m (6 ft x 7 ft)
doors to the hot aisle
Network supported Bulk cable pass-through-fiber
Bulk cable pass-through-copper
(Optional) External rated DEMARC box
Electrical specifications
Panel information
Feature Busway endfeed panels House panels
Number of
panels
•
4 (Standard density HP
POD)
•
6 (High density HP POD)
2
Capacity 225A, 3-phase 125A, 3-phase
Poles (per panel)
1, 3-pole enclosed circuit
breaker
30 pole positions
Input circuit breaker information