HP Performance-Optimized Datacenter Maintenance and Service Guide

Specifications 31
Specifications
HP POD specifications
Features Specifications
Dimensions 12 m x 2.4m x 2.7m (40 ft x 8 ft x 9.5 ft)
Maximum weight 11,340 kg (25,000 lb) empty- 50,348 kg (111,000 lb) fully-
loaded
Maximum power/ cooling
450 kW Standard HP POD
600 kW High density HP POD
Maximum rack quantity 22 racks
Rack Units (RU) per rack 50 RU
Rack Units (RU) maximum 1100 RU
Nominal power/ cooling per rack 25 kW
Maximum power/ cooling per rack 35 kW
Power input voltage 380-415 VAC, 3 Phase, 50/60 Hz, with neutral
Power distributed internally Through 4 or 6 225A electrical busways
220-240/380-415 VAC, 50/60 Hz
Customer access Double-door on one end
Customer access—Two 1 m x 2.1 m (3 ft x 7 ft) doors to the
cold aisle
Rear component access—Four 1.8 m x 2.1 m (6 ft x 7 ft)
doors to the hot aisle
Network supported Bulk cable pass-through-fiber
Bulk cable pass-through-copper
(Optional) External rated DEMARC box
Electrical specifications
Panel information
Feature Busway endfeed panels House panels
Number of panels
4 (Standard density HP
POD)
6 (High density HP POD)
2
Capacity 225A, 3-phase 125A, 3-phase
Poles (per panel) 1, 3-pole enclosed circuit
breaker
30 pole positions