HP Performance Optimized Datacenter 240e North America (Adiabatic) Maintenance and Service Guide
Removal and replacement procedures 19
Replacing the Adiabatic media
1. Insert the new Adiabatic media into the metal frame. Be sure that the directional airflow arrows on the
Adiabatic media are correct.
2. Replace the Adiabatic media bracket and screws.
3. Replace the water supply drip header assembly.
4. Replace the Adiabatic media access panel.
Air filter box
The Adiabatic unit comes with four air filters and two pre-filters installed.
The air filter sensor indicates when a filter must be changed through the ECS. HP recommends that you
periodically inspect and change each air filter. An air filter can be replaced during normal HP POD 240e
NA operation.
You need a screwdriver for installation.