HP Performance Optimized Datacenter (POD) 240a Site Requirements Guide
Site requirements 15
End 1 view clearances shown
Utilities
Consider proximity to required utilities, such as power, water, and network connections. While required
utilities can be brought to nearly any selected site, there is a potential for increased costs and decreased
efficiency when the HP POD 240a is located further from the utility source.
For utility clearance information, see "HP POD 240a dimensions and required clearances."
Water supply
The HP POD 240a requires supply water for the humidifier. The supply water must meet the following
requirements.
Requirement Specification
Pressure
Between 20 - 110 psi, 0.1 - 0.8
MPa
Temperature
Between 33°F - 104°F (1°C and
40°C)
Minimum flow rate
0.12gpm or 1.45 L/min
Connection
¾" G (Adapter to ¾" FPS)
Hardness
No greater than 40°fH (equal to
400 ppm of CaCO3)
Conductivity
100 to 1250 μS/cm
Organic compounds
None
Type of water
Drinking water. Do not use
demineralized or softened water.
Instant water fill flow rate
0.16gpm or 0.6 L/min
NOTE: If your water is out of range, consult a water quality expert.
NOTE: For more water quality requirements, see the Humidifier specification.