HP Performance Optimized Datacenter (POD) Networking Guide

Addressing airflow with HP Network Switchbox Enclosure Kit (SKU AT053A) 11
Devices that are installed in the HP Network Switch Enclosure and require more than 3RU of space will need
additional side panels from the (HP Network Switch Enclosure Sidepanel Kit (SKU AT960A).
The rack openings on the back side of the AT053A HP Network Switch Enclosure must be filled with blanking
panels.
Cisco MDS 9500 multilayer director
This device requires 3RU minimum space below and above the chassis to provide air flow. The device also
requires a Network Switchbox Enclosure Kit (SKU AT053A) as depicted in the previous illustration, as well
as the HP Network Switch Enclosure Sidepanel Kit side panels (SKU AT960A) on the inlet side only. Do not
install side panels on the exhaust side of the device.
To enable adequate airflow along the top, bottom, and side of the air-inlet side of the chassis, the MDS 9500
must be placed on a support rail and secured to the rack with custom mounting brackets, allowing the chassis
to be recessed in the rack. Care must be taken to also maintain hot and cold air-flow separation. The 9500
series switches have complex air flow and will require additional parts and customization. The account SA
is responsible for engaging directly with the POD network SA for additional guidance.
Rack-mount support brackets from Cisco are included with this device and are required for installation. These
brackets are not removable.
Power cables for this device must be secured at a level above the chassis to enable fan tray removal. All
network cables must be secured to the side of the rack.