For best results, install in close proximity to a low-resistance ground at
a point where the coaxial cable enters the building or attaches to an AP.
To connect your arrester to ground, use a very short and direct run of
#8 solid copper wire, or equivalent. For exterior installations, weather-
proof the coax connectors with a suitable mastic or rubberized tape to
prevent water incursion. See Figure 2.
Be sure to install in an accessible location that permits periodic
inspection and (as needed) replacement of the gas cartridge. Provide
drip loops in cables to prevent water from entering the building or AP.
See Figure 3.