HP ProLiant BladeSystem p-Class System Maintenance and Service Guide
Specifications 109
Table 5-1 Operating and Performance Specifications for a Server Blade Enclosure
Specification Value
Operating 28°C (82.4°F)
Non-operating 38.7°C (101.7°F)
1
Operating temperature has an altitude derating of 1°C per 304.8 m (1.8°F per 1,000 ft). No direct sunlight. Upper
operating limit is 3,048 m (10,000 ft) or 70 Kpa/10.1 psia. Upper non-operating limit is 9,144 m (30,000 ft) or
30.3 KPa/4.4 psia.
2
Storage maximum humidity of 95% is based on a maximum temperature of 45°C (113°F). Altitude maximum for storage is
70 KPa.
Table 5-2 Operating and Performance Specifications for an Enhanced Server Blade Enclosure
Specification Value
Dimensions
Height 26.67 cm (10.5 in)
Depth 73.30 cm (28.86 in)
Width 44.70 cm (17.60 in)
Weight with RJ-45 patch panels
No HP BladeSystem 20p blades 36.33 kg (80.10 lb)
8 HP BladeSystem 20p blades 99.84 kg (220.10 lb)
Input requirements
Rated input voltage -43 VDC to -53 VDC Nominal -48 VDC
Rated input current (per side) 64.1 A at -48 VDC
Rated input power (total) 6000 W
Individual server blade bay ratings
Rated input voltage -43 VDC to -53 VDC Nominal -48 VDC
Rated input current 14.6 A at -48 VDC
Rated input power 700 W
Temperature range
1
Operating 10° to 35°C (50° to 95°F)
Non-operating -30° to 60°C (-22° to 140°F)
Relative humidity, noncondensing
2
Operating 20% to 80%
Non-operating 5% to 95%
Wet bulb temperature
Operating 28°C (82.4°F)
Non-operating 38.7°C (101.7°F)
1
Operating temperature has an altitude derating of 1°C per 304.8 m (1.8°F per 1,000 ft). No direct sunlight. Upper
operating limit is 3,048 m (10,000 ft) or 70 Kpa/10.1 psia. Upper non-operating limit is 9,144 m (30,000 ft) or
30.3 KPa/4.4 psia.
2
Storage maximum humidity of 95% is based on a maximum temperature of 45°C (113°F). Altitude maximum for storage is
70 KPa.