Table 5-7 Operating and Performance Specifications for HP BladeSystem p-Class 1U Power Enclosures
Specification Value
Rated input voltage 200 VAC to 240 VAC
Rated input frequency 50 Hz to 60 Hz
Rated input current per side 3 x 13 A
Rated input power per side 3 x 2310 W
Power connector IEC-320 C20
Output voltage specifications
Rated output voltage -48.8 VDC to -54 VDC
Rated output current 117 A
Rated output power 6,000 W
Nominal power 6,000 W at 208 VAC
Ambient temperature range
1
Operating 10° to 35°C (50° to 95°F)
Shipping -30° to 60°C (-22° to 140°F)
Relative humidity, noncondensing
2
Operating 20% to 80%
Non-operating 5% to 95%
Wet bulb temperature
Operating 28°C (82.4°F)
Non-operating 38.7°C (101.7°F)
1
Operating temperature has an altitude derating of 1°C per 304.8 m (1.8°F per 1,000 ft). No direct sunlight. Upper
operating limit is 3,048 m (10,000 ft) or 70 Kpa/10.1 psia. Upper non-operating limit is 9,144 m (30,000 ft) or
30.3 KPa/4.4 psia.
2
Storage maximum humidity of 95% is based on a maximum temperature of 45°C (113°F). Altitude maximum for storage is
70 KPa
Table 5-8 Operating and Performance Specifications for HP BladeSystem p-Class 3U Power Enclosures (North
America/Japan)
Specification Value for Single-Phase Model Value for Three Phase Model
Dimensions
Height 13.34 cm (5.25 in) 13.34 cm (5.25 in)
Depth 68.96 cm (27.15 in) 68.96 cm (27.15 in)
Width 44.7 cm (17.60 in) 44.7 cm (17.60 in)
Weights
No hot-plug power supplies 21.55 kg (47.5 lb) 21.55 kg (47.5 lb)
All hot-plug power supplies 45.13 kg (99.5 lb) 56.93 kg (125.5 lb)
Input Requirements
Rated input voltage 200 VAC to 240 VAC 200 VAC to 240 VAC line to line,
three-phase (3W+G)
Rated input frequency 50 Hz to 60 Hz 50 Hz to 60 Hz
Rated input current per side 24 A 24 A per phase
Rated input power per side 5,760 W 9,976 W
Power plug 1 NEMA L6-30P per side 1 NEMA L15-30 per side