HP BladeSystem c-Class Site Planning Guide

Hardware specifications and requirements 52
Specification Value
Height 584.00 mm (23.00 in)
Depth 1013.00 mm (39.88 in)
Width 607.00 mm (23.88 in)
Standard enclosure weight *
Unboxed 65.80 kg (145.00 lb)
Shipping 88.50 kg (195.00 lb)
Maximum enclosure weight
Unboxed 136.00 kg (300.00 lb)
Shipping 158.80 kg (350.00 lb)
* Includes two power supplies, four fans, and one Onboard Administrator.
HP 10000 G2 rack specifications
For a current list of all rack specifications, see the Best Practices document on the HP website
(http://www.hp.com/support/HP10000G2SeriesRack_Manuals
).
Rack Height Width Depth Dynamic load
(gross)
Static load
HP 10622
G2
22U 600 mm (23.8
in)
1000 mm (39.4
in)
544.3 kg (1200
lb)
544.3 kg (1200
lb)
HP 10636
G2
36U 600 mm (23.8
in)
1000 mm (39.4
in)
689.5 kg (1520
lb)
907.2 kg (2000
lb)
HP 10642
G2
42U 600 mm (23.8
in)
1000 mm (39.4
in)
907.2 kg (2000
lb)
907.2 kg (2000
lb)
HP 10647
G2
47U 600 mm (23.8
in)
1000 mm (39.4
in)
Not applicable 907.2 kg (2000
lb)
HP 10842
G2
42U 800 mm (31.5
in)
1000 mm (39.4
in)
453.6 kg (1000
lb)
907.2 kg (2000
lb)
Rack requirements
The enclosure is compatible with the following racks:
All HP 10000 and 10000G2 Series racks except the HP 10614 rack.
NOTE: The system is optimized for 10000 Series racks.
Telco racks
If a third-party rack is used, observe the following additional requirements to ensure adequate airflow and
to prevent damage to the equipment:
Front and rear doors: If the rack includes closing front and rear doors, a minimum of 65 percent
open area must be provided to ensure adequate airflow.