HP BladeSystem c-Class Site Planning Guide
Configuration scenarios 54
Configuration scenarios
Example configurations
The following configuration examples were calculated using the HP Blade Power Sizer Tool. This tool is
designed for facilities planning purposes only. Values obtained from the tool are based on worst case
loads. Whenever possible, actual measurements are recommended. Measurements should be made with
the intended configuration, application loading, and ambient environment.
Actual power usage will vary depending on application loading, ambient temperature, and other factors.
Example minimum configuration
This power summary is based on the following configuration:
• HP BladeSystem c7000 enclosure (1)
• Ethernet Pass-Through Modules for HP BladeSystem (2)
• HP ProLiant BL460c Server Blades (2)
o 2.33-GHz Intel® Xeon™ processor 5148, dual-core (2 per server blade)
o 4GB (4 x 1GB) RAM per server blade
o 36GB 10,000-rpm SAS hard drives (2 per server blade)
Total system leakage current per branch 0 mA
Total system inrush current per branch (2 mS) 70 A
Total system weight (includes power and rack) 197 kg (435 lb)
Power credentials Idle 100% utilization Circuit sizing
Total input power 601 W 764 W 1109 W
Total input VA 613 VA 779 VA 1132 VA
BTU 2049 BTU 2604 BTU 3781 BTU
Total input current 2.95 A 3.75 A 5.44 A
Total airflow (CFM) 116 131 156
Total airflow (CMM) 3.280 3.713 4.429
Example typical configuration
This power summary is based on the following configuration:
• HP BladeSystem c7000 enclosure (1)
• HP Virtual Connect Ethernet Modules (2)
• HP Virtual Connect Fibre Channel Modules (2)