UPS R3000 XR Models User Guide

Specifications
C-4 HP Uninterruptible Power System R3000 XR Models User Guide
Table C-4: Output Specifications
Characteristics Configuration Setting
(VAC)
Available Nominal
Output Voltage (VAC)
Voltage 100 100
110 110
120 120
127 127
200 200
208 208
230 230
240 240
Source of Power Regulation
Output tolerance Utility power
(normal range)
-10% to +6% of nominal output voltage
rating (within the guidelines of the
Computer Business Equipment
Manufacturers Association)
Battery power
±5% of nominal output voltage rating
Feature Specification
Other features Online efficiency 94% nominal input voltage
Voltage wave shape Sine wave; 5% THD with typical PFC load
Surge suppression High-energy 6500 A peak
Noise filtering MOVs and line filter for normal and
common mode use