UPS R3000 XR Models User Guide

Specifications
HP Uninterruptible Power System R3000 XR Models User Guide C-5
Battery Specifications
Table C-5: Battery Specifications
Feature Specification
Type Each model contains maintenance-free, sealed, valve regulated lead-acid
(VRLA) batteries with an eight-year minimum float service life at 25ºC
(77ºF).
Voltage The battery module has a battery string voltage of 120 V.
Charging Complete charge takes no more than 24 hours.
Approximately 3 hours to 80 percent capacity at default nominal utility
voltage and no load.
Battery Runtime
Table C-6: Estimated Battery Runtime
Load
(Percent)
Estimated Battery Runtime
(Minutes)
UPS with ERM Runtime
(Minutes)
20 40 120
50 12 45
80 6.5 30
100 5 20