UPS R6000 ERM Installation Instructions
To mount the rails:
1. Loosen the wing nuts (1) and extend the brackets to the desired
length (2). Tighten the wing nuts slightly to stabilize
the bracket.
2. Use the rack template tool to measure and mark the screw
locations for the rails on the front and rear of the rack.
3. Use the cage nut tool to install the cage nuts in the rear
rack-mounting rails.
4. Insert at least one screw through each rack-mounting rail and
into the front of each rail.
5. Insert the screws into the back of each rail and through the cage
nuts that were installed in step 3.
Installing the ERM in the Rack
Before attempting to install the ERM, review and adhere to all
safety information provided in the “Important Safety Information”
section of this document.
To install the ERM in the rack:
1. With one person on each side of the carton, remove the ERM
chassis from the carton.
2. Gently lower the chassis to the floor in front of the rack.
3. With one person on each side, lift the chassis to rail level and
slide into place.
4. Secure the chassis to the rack using the screws and cage nuts
supplied with the rack.
NOTE: After installing the ERM chassis, insert remaining screws for
additional support, if any screw holes are unoccupied.
WARNING: To prevent personal injury, make sure that the
battery circuit breakers are in the off position.
5. Verify that the battery circuit breaker is in the off position on
the following equipment:
a. The ERM being installed
b. Any other ERM that will be attached
c. Any UPS that will be attached
6. Place the UPS in Manual Bypass mode.
7. Remove the ERM connector cover from the UPS. If you are
installing a second ERM, remove the ERM connector cover
from the first ERM.
8. Plug the ERM cable into the UPS. If you are installing a second
ERM, plug the ERM cable on the second ERM into the
first ERM.
9. Secure the cable by attaching the retaining bracket. Use the
screw that was removed in step 7.