UPS R6000 Models User Guide

LCD Configuration and Status
3-2 HP Uninterruptible Power System R6000 Models User Guide
Matching the Utility Voltage
Use configuration parameters to select the UPS voltage range (see Table 3-1).
If the utility voltage is within this range, the UPS supplies utility power to the output
receptacles.
If the utility voltage is outside this range, the UPS supplies battery power to the output
receptacles.
If the utility voltage frequently varies outside the operating range, update the UPS
configuration to match.
NOTE: When you set the voltage through the LCD panel (as described in the “Set Voltage” section of
this chapter), you are setting the UPS output voltage.
Table 3-1: Voltage Ranges (VAC)
Nominal Utility Voltage Level
(VAC)
Normal Utility Voltage Range Extended Utility Voltage
Range
200 V Nom. ±20
166-240 V N/A
208 V Nom. ±20
166-248 V N/A
220 V Nom. ±20
176-264 V N/A
230 V Nom. ±20
184-276 V 166-288 V
240 V Nom. ±20
192-288 V N/A
To update the configuration:
1. Have a licensed electrician measure your utility voltage.
2. Use Table 3-1 to identify the operating range that most closely matches your nominal
utility voltage level.
3. Update the UPS output voltage as required. Refer to the section, “Set Voltage,” in this
chapter for more information.