UPS R6000 Models User Guide

Specifications
HP Uninterruptible Power System R6000 Models User Guide C-3
Table C-3: Output Specifications continued
Output Voltage
Utility Voltage (VAC) Nominal Output Voltage
(VAC)
Nominal Output Voltage on
Battery (VAC)
200 200 204
208 208 204
220 220 230
230 230 230
240 240 230
Source of Utility Power
Source Regulation
Utility power (normal range)
±10% of nominal output voltage (within the guidelines of
the Computer Business Equipment Manufacturers
Association)
Utility power (extended range) +10% to -15% of nominal output voltage and/or +5/-3%
frequency (within the guidelines of the Computer
Business Equipment Manufacturers Association)
Battery power
±5% of nominal output voltage
Additional Features
Feature Specification
On-line efficiency 96%
Voltage wave shape while on battery Sinusoidal with less than 3% THD at linear load
Surge suppression High energy 6500 A peak (meets the requirements of
ANSI C62.41 Category B (formerly IEEE 587))
Noise filtering The input noise suppression is comprised of Normal
Mode Filtering, Common Mode Filtering, or a combination
of both.
Battery Specifications
Table C-4: Battery Specifications
Feature Specification
Type Sealed lead-acid, maintenance-free
Voltage Internal batteries 12 VDC each, 360 VDC total
Charging 24 hours to full charge
4 hours to 90% capacity at default nominal utility voltage and no load