director 2/64 installation guide
director 2/64 installation guide 2–71
Installing and Configuring the Director 2/64
2. Verify that the preferred domain ID for the director is unique and does not conflict
with the ID of another director or switch participating in the fabric. To change the
domain ID, see “Configure Fabric Operating Parameters” on page 2–48.
3. Verify that the R_A_TOV and E_D_TOV values for the director are identical to
the values for all directors and edge switches participating in the fabric.
4. Route a multimode or single-mode fiber-optic cable (depending on the ISL
distance between directors) between customer-specified E_Ports of both directors.
5. At the Products View page, click the Director 2/64 icon. The Hardware View
page for the selected director displays.
6. Click the UPM card graphic supporting the E_Port connection to open the Port
Card View page.
7. Click the E_Port connector to open the Port Properties dialog box, as shown in
Figure 2–47.
8. Verify that the Link Incident field displays None and the Segmentation Reason
field is blank or displays N/A. If an ISL segmentation or other problem is
indicated, consult the hp StorageWorks director 2/64 service manual to isolate the
problem. If no problems are indicated, installation is complete.
Figure 2–47: Port Properties dialog box