director 2/64 installation guide
3–4 director 2/64 installation guide
Using EWS to Configure the Director 2/64
Figure 3–3: Ports page
c. Click the check box in the 10-100 km column to enable extended distance
buffering for a port (the default is disabled). A check mark in the box enables
extended distance operation up to 100 kilometers (through repeaters).
2. Scroll down to the bottom of the page and click Activate to save the information.
The message “Your changes to the port configuration have
been successfully activated” displays.
Configure Director Identification
Perform this procedure to configure the director name, description, location, and
contact person. The Name, Location, and Contact variables configured here
correspond respectively to the SNMP variables sysName, sysLocation, and
sysContact. SNMP management workstations use these variables to obtain data from
directors.