director 2/64 installation guide

director 2/64 installation guide 2–17
Installing and Configuring the Director 2/64
Install the Anti-tip Feet on an HP Rack System/e Rack
Use the following procedure to mount anti-tip feet on an HP rack system/e rack only,
as shown in Figure 2–8:
1. Place the anti-tip feet (1), provided in the HP rack system/e and industry-standard
19-in rack mount kits, on the front and rear of the rack base.
2. Secure the anti-tip feet (1) to the base of the rack (front and rear).
3. Lower the rack feet (2) until they touch the floor.
Figure 2–8: Mounting anti-tip feet for a HP rack system/e rack
Install Mounting Bracket Hardware in the Rack
Use these steps to install the mounting hardware in a rack.
IMPORTANT: The 9Us used to mount the switch are called U1 through U9; U1 is the lowest of
the 9Us. Note also that 1U below the switch is required for the rail tray for a total of 10U to mount
the switch.
1. Determine the appropriate placement for the switch inside the rack. It is important
to consider the number of switches you intend to install. See “Tips for Installing
More than One Switch” on page 2–9.
2. Determine the mounting location for the rail tray, as shown in Figure 2–9.
IMPORTANT: The rail tray will be mounted 1U below the switch. Because the switch
should be mounted no higher than U11, the tray should be mounted no higher than U10.
Make sure there are at least 2Us above the top of the switch empty for the sliding shelf.